[Tasker] Woodward 505 LST [Tech Support Index]

Woodward 505 LST
Modbus Network Address and Network Time Out Value
Written 7/2012 / Updated 11/9/12

Ports:  All versions of the 505 (505, 505E, and 505 LST) run on the same hardware and have 2 Modbus communication ports.  With the 505 and 505E versions, the ports are completely interchangeable.  In the LST version of the 505, the ports are mostly interchangeable, but there are a few parameters dedicated to one port or the other.  The LST version Modbus ports are labeled as DCS and HMI.  Woodward's intent is to use the DCS port as the primary control port.
Comm Port 1 is referred to as the DCS Port. 
Comm Port 2 is referred to as the HMI Port.
The Modbus Ports can be assigned different Network Addresses.

Unlike the 505 and 505E, the Woodward 505 LST Modbus Network Address and the Network Time Out Alarm values are not configurable in either the Configuration Program Mode or the Service Mode.  The 505 LST Modbus Device Address the Time Out values can be changed in the Debug Mode.  The Debug Mode includes tunable values that are not intended to be utilized by the average end user, however, a few of the configurable values various end users may need to modify are accessed via the Debug Mode.  The Debug Mode interface is more cryptic and less intuitive than the more end user friendly Program Mode or Service Mode.

Refer to the [Generic 505 Debug Mode Overview] for instructions on entering the Debug Mode
and the Figures below illustrating the navigation arrangement

The Debug Tunable Blocks are in the S_MODBUS Category

There is an Individual Blocks dedicated to the DCS port and another block dedicated to the HMI port
DCS.INIT_MOD for the DCS Port
HMI.INIT_MOD  for the HMI Port
Both blocks contain fields that are twins for each other

The Tunable Fields for the Time Out and  Network Address are:
DCS Time Out Alarm Field:  DCS.TIME_OUT or HMI.TIME_OUT
Network Address Field:  DCS.NET_ADDR or HMI.TIME_OUT
(the Time Out Field Precedes the Network Address Field) when scrolling to the right)

Both of the Fields are reached by moving laterally with the Diamond Navigation Key from within the
DCS.INIT_MOD or the HMI.INIT_MOD Blocks which are nested under the S_MODBUS Category

Instructions / Generic to multiple 505 version variations

Debug Mode Procedure Instructions / Generic to multiple 505 version variations
Written 7/2012 / Updated 11/2012

Instructions / Specific the 505 LST Modbus Network Address and Communication Time Out Alarm
Updated 9/11/12